Article: 120 — Load Calculations
Part: Part VI — Health Care Facilities
Section: 120.110
Format: Quick Hit
Health care facilities have their own special receptacle-load demand factors.
Section 120.110 allows certain receptacle loads to be subjected to Table 120.110, creating a different calculation method from the general non-dwelling receptacle rules covered earlier in Article 120.
In health care facilities, receptacle loads calculated under:
120.14(H) — Fixed multioutlet assemblies
120.14(I) — Receptacle outlets
can be subjected to the demand factors in Table 120.110 when the branch circuits are 150 volts to ground or less.
This isn't simply another application of the general receptacle demand-factor table.
Health care facilities have their own specific provision and table.
The table begins with a familiar concept:
➡️ 100%
There is no demand-factor reduction applied to the first 10,000 VA.
➡️ Demand factor not available in the source material used for this Quick Hit
⚠️ Source note: The supplied source text does not contain the percentage for the "Remainder over 10,000" row.
Rather than guessing at an NEC value, this series leaves the missing percentage clearly identified until the complete table can be verified.
Earlier in the series, we looked at Table 120.47 for certain non-dwelling receptacle loads.
That table also uses a structure where:
Initial load → 100%
Additional load → reduced demand factor
The important lesson isn't to assume the tables are interchangeable.
Different occupancies can have different demand-factor rules.
When you see 120.110, remember:
🏥 Health care facility
🔌 Receptacle loads from 120.14(H) or 120.14(I)
⚡ 150 volts to ground or less
📊 Table 120.110
And the first 10,000 VA is calculated at 100%.
Per Table 120.110, what demand factor applies to the FIRST 10,000 VA of qualifying receptacle load in a health care facility?
A) 50%
B) 100%
C) 75%
D) 0%
B) 100%
Continue the Article 120 Quick Hits:
🌐 www.JoshTheSparky.com/quick-hits
Test yourself with Brain Busters:
🧠 www.JoshTheSparky.com/brain-busters
Answer the Question of the Week:
❓ www.JoshTheSparky.com/question-of-the-week
Read Sparky's Journal:
📓 www.JoshTheSparky.com/sparkys-journal
Catch the latest Sparky Weekly:
📰 www.JoshTheSparky.com/sparky-weekly
View Sources & References:
📚 www.JoshTheSparky.com/Sources
Primary: Article 120, 120.110
Related: 120.14(H) — Fixed Multioutlet Assemblies
Related: 120.14(I) — Receptacle Outlets
Related: Table 120.110 — Health Care Facility Receptacle Demand Factors
Related: 120.47 — Non-Dwelling Receptacle Demand Factors
The "Remainder over 10,000 VA" demand-factor percentage was not included in the source material used to create this Quick Hit.
No value has been guessed or substituted.
Once the complete Table 120.110 is available, this page can be updated with the verified percentage and a worked example.
Article 120 — Load Calcs Won't Kill You
🏥 Part VI — Health Care Facilities
Episode 41: Hospital Receptacles Get Their Own Discount Table
Next: Episode 42 — Health Care Facility Unit Loads