Episode 13
Got four or more qualifying fastened-in-place appliances in a dwelling?
You may be able to apply a 75% demand factor to their combined nameplate load.
But there's an important exclusion list.
For one-family, two-family, or multifamily dwellings, a 75% demand factor is permitted when the qualifying appliances:
Are fastened in place
Are rated 1/4 hp or greater, or 500 watts or greater
Are supplied by the same feeder or service
Total four or more appliances
When the requirements are met:
Combined nameplate load × 75%
That's effectively a 25% reduction from the combined nameplate load for this calculation.
The 75% demand factor does not apply to:
1️⃣ Fastened-in-place household cooking equipment
2️⃣ Clothes dryers
3️⃣ Space-heating equipment
4️⃣ Air-conditioning equipment
5️⃣ Electric vehicle supply equipment (EVSE)
These loads have their own calculation requirements elsewhere.
Don't simply throw them into the fastened-in-place appliance calculation to get the 75% demand factor.
A dwelling has:
A fastened-in-place water heater
A garbage disposal
A dishwasher
An exhaust fan
All are 500 watts or greater and supplied by the same service.
Per 120.53, what demand factor can be applied to their combined nameplate load?
A) 100%
B) 50%
C) 75%
D) 0% — appliances never get a demand factor
👇 What's your answer?
There are 4 qualifying appliances.
They meet the stated rating threshold and are supplied by the same service.
Therefore:
4 qualifying appliances → 75% demand factor
If their combined nameplate load were 10,000 VA:
10,000 VA × 75% = 7,500 VA
C) 75%
The four appliances meet the conditions for the permitted 75% demand factor.
The important part isn't just remembering 75%.
Remember the excluded loads.
Cooking equipment, clothes dryers, space heating, air conditioning, and EVSE aren't simply bundled into this calculation.
Continue exploring the JoshTheSparky Quick Hits library.
Test what you know with JoshTheSparky Brain Busters.
Take the latest JoshTheSparky Question of the Week.
Go deeper into electrical thoughts, lessons, discoveries, and experiences in Sparky's Journal.
Follow the latest progress, discoveries, projects, and industry updates in Sparky Weekly.
Review the references and resources used throughout JoshTheSparky.com in the JoshTheSparky Sources library.
← Back to Article 120 Quick Hits
← Back to the 2026 NEC Quick Hits
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.
The National Electrical Code® and NEC® are registered trademarks of NFPA. JoshTheSparky.com is not affiliated with, sponsored by, or endorsed by NFPA.