Article: 120 — Load Calculations
Part: Part VII — Marinas, Boatyards, Floating Buildings & Docking Facilities
Section: 120.120
Format: Quick Hit
Marinas, boatyards, floating buildings, and docking facilities have their own demand-factor rules for shore-power receptacles.
Section 120.120 provides a specific method for calculating the load of receptacles supplying boats — including several important notes that can change how the load is calculated.
General lighting and other loads at marinas, boatyards, floating buildings, and docking facilities continue to be calculated using the standard Part III methods.
However, receptacles supplying shore power to boats can use the demand factors in Table 120.120.
⚠️ Important: When Table 120.120 is used, the 120.61(B) neutral-load reduction cannot also be applied.
You don't get to stack both demand-factor methods on top of each other.
The table provides different demand factors based on the number of shore-power receptacles.
➡️ 100%
➡️ 80%
➡️ 70%
➡️ 50%
➡️ 30%
The basic idea is diversity.
As the number of shore-power receptacles increases, the percentage of the calculated load that must be included decreases because it is unlikely that every boat will simultaneously operate at its maximum calculated load.
If a slip has two shore-power receptacles with different voltage or ampere ratings, only the receptacle with the greater kW demand is included.
In other words, don't automatically add both receptacles together when the rule directs you to use the greater kW demand.
If each slip's shore-power pedestal is equipped with an individual kWh submeter, the final demand amperes are multiplied by:
➡️ 0.9
That's a 10% reduction to the resulting demand amperes.
If the same circuit supplies both a boat hoist and shore power at a slip, only the load with the greater kW demand is included.
Again, the rule prevents you from simply adding both loads together when the larger-load method applies.
When you see 120.120, think:
⛵ Marina / boatyard / floating building / docking facility
🔌 Shore-power receptacles
📊 Table 120.120
⚡ More receptacles = lower demand factor
🚫 Don't combine Table 120.120 with the 120.61(B) neutral reduction
And remember the special notes:
Two receptacles at one slip? → Use the greater kW demand.
Individual kWh submeter? → Multiply final demand amperes by 0.9.
Boat hoist + shore power? → Use the greater kW demand.
Per Table 120.120, what demand factor applies to a marina with 20 shore-power receptacles?
A) 100%
B) 90%
C) 70%
D) 60%
C) 70%
A marina with 20 shore-power receptacles falls within the 15–30 receptacle range of Table 120.120.
Therefore, the applicable demand factor is:
70%
Continue the Article 120 Quick Hits:
🌐 www.JoshTheSparky.com/quick-hits
Test yourself with Brain Busters:
🧠 www.JoshTheSparky.com/brain-busters
Answer the Question of the Week:
❓ www.JoshTheSparky.com/question-of-the-week
Read Sparky's Journal:
📓 www.JoshTheSparky.com/sparkys-journal
Catch the latest Sparky Weekly:
📰 www.JoshTheSparky.com/sparky-weekly
View Sources & References:
📚 www.JoshTheSparky.com/Sources
Primary: Article 120, 120.120
Related: Table 120.120 — Shore-Power Receptacle Demand Factors
Related: 120.61(B) — Neutral Load Calculation
Article 120 — Load Calcs Won't Kill You
⛵ Part VII — Marinas, Boatyards, Floating Buildings & Docking Facilities
Episode 41: Hospital Receptacles Get Their Own Discount Table
Episode 42: Patient Care Circuits Get Their Own Rule Too
Episode 43: Marinas: Shore Power Gets Its Own Discount Curve
The series continues through Part VII — Marinas, Boatyards, Floating Buildings & Docking Facilities.
Next section: 120.121 and beyond.