Episode 32 — 120.84 Multifamily Dwelling Units
We've already seen optional methods for:
🏠 Single dwelling units
🏚️ Existing dwelling units
Now we're moving to:
If you're dealing with a building containing 3 or more dwelling units, 120.84 provides another optional calculation method.
But there's a catch.
You don't get to use the shortcut just because it's an apartment building.
You've got to clear all three hoops.
If a dwelling unit is supplied by multiple feeders, the qualification requirement isn't met.
Think:
for purposes of this qualification.
🍳 Ranges
🔥 Electric ovens
⚡ Electric cooktops
The requirement is about the dwelling units having electric cooking equipment.
Every dwelling unit must have:
🌡️ Electric space heating
OR
❄️ Air-conditioning
OR
🌡️❄️ Both
Before using the optional multifamily calculation, ask:
Miss one?
There's an important provision for buildings without electric cooking equipment.
Under the specified conditions, if the standard Part III calculation produces a higher result than the optional method plus the applicable cooking allowance, the permitted calculation can use the lower result.
It's a specific provision — not a blanket rule saying every multifamily building without electric cooking automatically qualifies.
Yep.
We've seen this pattern before.
When the applicable single-phase dwelling units are supplied from a:
the calculation uses the maximum number of units connected between any two phases.
The total demand is:
You can't always just:
Add every dwelling unit together.
The way those units are distributed across the phases matters.
Find the largest two-phase combination
⬇️
Multiply that number by 2
That's the special calculation approach described here.
Here's another important distinction.
An apartment building doesn't only have dwelling units.
There may also be:
💡 Hallway lighting
🛗 Elevators
🔌 Common-area receptacles
🧺 Laundry facilities
🏢 Other house/common loads
These are not simply thrown into the per-dwelling-unit shortcut.
They follow the applicable standard Part III load-calculation method.
Per 120.84(A)(1), which of these is REQUIRED for a multifamily building to qualify for the Table 120.84(C) optional calculation?
A) Each dwelling unit has electric cooking equipment
B) At least one unit shares a feeder with another
C) No units have space heating or AC
D) The building must have fewer than 3 units
👇 What's your answer?
Electric cooking equipment in every dwelling unit is one of the conditions for using the optional multifamily calculation method.
ONE FEEDER
➕
ELECTRIC COOKING
➕
ELECTRIC HEAT / AC
Requirement
Required?
3+ dwelling units
✅
One feeder per dwelling unit
✅
Electric cooking in every unit
✅
Electric space heating, AC, or both in every unit
✅
House/common loads included in per-unit shortcut
❌
House/common loads calculated separately
✅
Notice how Part IV is building a progression:
Single dwelling unit
Existing dwelling unit
Multifamily dwelling units
Different situations.
Different optional methods.
Same overall goal:
Episode 32 established who qualifies.
Next we get into:
That's where Table 120.84(C) becomes the star of the show.
Continue exploring the JoshTheSparky Quick Hits library.
Test yourself with the JoshTheSparky Brain Busters.
Take the latest JoshTheSparky Question of the Week.
Explore Sparky's Journal.
Catch the latest Sparky Weekly.
Review the references used throughout JoshTheSparky.com in the JoshTheSparky Sources library.
← Back to Article 120 Quick Hits
← Episode 31 — Existing Dwelling Units
→ Episode 33 — Table 120.84(C): Multifamily Demand Factors
Episode 25: Welcome to Part IV
Episode 26: Who Gets to Use This Shortcut?
Episode 27: Bucket #1 — General Loads
Episode 28: Bucket #2 — Heating & AC (Part 1)
Episode 29: Bucket #2 — Heating & AC (Part 2)
Episode 30: Bucket #3 — EVSE + Putting It All Together
Episode 31: Existing Dwelling Units
Episode 32: Multifamily Dwelling Units ← YOU ARE HERE
Episode 33: Table 120.84(C)
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.