Episode 12
Two common dwelling-unit branch-circuit requirements get the same minimum load treatment:
Small-appliance circuits + laundry circuit = 1,500 VA each
Let's break it down.
Each 2-wire small-appliance branch circuit required by 210.11(C)(1) is calculated at:
If multiple small-appliance circuits are supplied from different feeders, each circuit still contributes at least 1,500 VA to the calculation.
These loads can be included with the general lighting load.
When included with the general lighting load, the applicable Table 120.45 demand factors can then apply.
The required laundry branch circuit under 210.11(C)(2) is also calculated at:
Like the small-appliance circuits, the laundry load can be included with the general lighting load and subjected to the applicable Table 120.45 demand factors.
The individual branch circuit permitted by 210.52(B)(1) Exception No. 2 does not have to be included in this calculation.
2 small-appliance branch circuits
1 laundry branch circuit
Per 120.52, what is the minimum VA that must be included for all three circuits combined, before any demand factors?
A) 3,000 VA
B) 4,500 VA
C) 1,500 VA
D) 6,000 VA
👇 What's your answer?
2 × 1,500 VA = 3,000 VA
1 × 1,500 VA = 1,500 VA
B) 4,500 VA
Before any applicable demand factors are applied, the three required circuits contribute a combined minimum load of:
← Back to Article 120 Quick Hits
→ Not All Lighting Gets Treated Equally: Demand Factors
→ Understanding Load Calculations
→ The Rules Behind Every Load Calculation
🧠 Brain Busters — Test your knowledge
❓ Question of the Week — Take the weekly NEC challenge
📖 Tutorials — Go deeper
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.
The National Electrical Code® and NEC® are registered trademarks of NFPA. JoshTheSparky.com is not affiliated with, sponsored by, or endorsed by NFPA.